A 200-kVA, 230-V/230-kV testing transformer having a resistance and leakage reactance of 2% and 7% respectively, is to be used as a resonant transformer at 50 Hz to test a piece of cable at 400 kV. The load capacitance is 0.01μF and inductor coil is assumed to 3% resistance. Determine the series inductance required and the input voltage. ..

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.28MCQ
icon
Related questions
Question
100%
A 200-kVA, 230-V/230-kV testing transformer having a resistance and leakage reactance of 2% and 7% respectively, is to be used as a resonant transformer at 50 Hz to test a piece of cable at 400 kV. The load capacitance is 0.01μF and inductor coil is assumed to 3% resistance. Determine the series inductance required and the input voltage. ..